Note: When testing detectors or sensors, refer to NFPA 72, or contact your local branch office.
CAUTION: Before functionally testing the detectors or sensors, be sure to disconnect the city connection, releasing devices, and
extinguishing systems. For the 4120, 4006, 4008, 4020, 4010, 4100+, 4100U, 4100ES, 4010ES, or 4007ES panel, put the panel in the Walk
Test mode.
6.3.3 Preferred method of testing smoke detectors or sensors
NFPA minimally requires annual functional testing of smoke detectors or sensors at their installed location. To perform this annual test, use
the Solo 336 Aerosol Smoke Dispenser.
Important: After testing detectors, reset the fire alarm panel to restore the fire alarm system to a normal status. After testing sensors,
ensure you clear the peak values.
6.3.4 Test Equipment Available
The following test equipment is available. Follow the instructions included with the equipment for testing.
553-760: Test and Removal Tool, attached to Mr. Longarm 4 foot, or 121.92 centimeter pole (Item number 7508) or 6 foot, or 182.88
centimeter pole (Item number 7512).
553-761: Heat Detector or Sensor Removal Adapter, use this with the Test and Removal Tool, 553-760.
553-805: Removal Adapter Head Attachment (attaches to the 553-760 tool).
553-810: Magnet Tester, attached to Mr. Longarm 4 foot, or 121.92 centimeter pole (Item number 7508) or 6 foot, or 182.88
centimeter pole (Item number 7512).
Gemini Sensitivity Tester (Model 501 or 502).
Solo 336 Aerosol Smoke Dispenser –attached to either the Solo 100 (15 ft.) telescopic fiberglass pole or the Solo 101 (4 ft.) fiberglass
pole.
Solo Red Cup (709-024). Use to hold the 553-635 Aerosol Spray Can.
Solo (708-021) Adapter for Solo Poles. Use to adapt 553-760 Test and Removal Tool to the Solo Pole.
TrueTest 801, Smoke Detector Sensitivity Test Equipment.
Smoke 400, Smoke aerosol for TrueTest.
Testifire 2000-024, Smoke, Heat and CO Detector Tester.
Testifire 2001-024, Smoke, Heat and CO Detector Test Kit (includes 2 battery batons and
ac/dc charger).
TS3-024 Smoke capsule, for use with Testifire Smoke, Heat and CO Detector Tester.
TC3-024 CO Capsule, for use with Testifier Smoke, Heat and CO Detector Tester.
Note: The TrueTest 801 or the Testifier 2000-024 are the only testers for use with the 4098-9770 and 4098-9771 bases.
Table 13: Available smoke test aerosols
Product name Model Description
PurCheck® HO-30S Smoke alarm tester
SmokeCheck® HO-25S Smoke alarm tester
CHEKKIT® - Smoke detector tester
Solo A4 - Smoke detector tester
page 36 574-709 Rev. AP
4098 Detectors, Sensors, and Bases Application Manual

Table of Contents

Other manuals for Simplex 4098

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4098 and is the answer not in the manual?

Simplex 4098 Specifications

General IconGeneral
BrandSimplex
Model4098
CategoryFire Alarms
LanguageEnglish

Related product manuals