and their sensors receive both power and data over MAPNET II/IDNet wiring. The 4098-9791 sensor base requires 24VDC power for relay
operation, and the 4098-9771 through 4098-9773 and 4098-9794 sensor bases with sounders require 24 VDC or Notification Appliance
Circuit (NAC) power. The 4098-9770 through 4098-9773, 4098-9780, 4098-9791 and 4098-9794 are NOT compatible with the 2120 CDT.
The 4098-9793 and 4098-9777 are only compatible with the 4010, 4008, 4100U, 4100ES and 4010ES, 4007ES, except with the 4100-3103
Quad Panel Isolator.
The 4098-9766 and 4098-9767 are only compatible with the 4100ES, 4010ES and 4007ES providing IDNet2.
*From this point on, the 4007ES and the 4007ES Hybrid panels are referred to as 4007ES.