24
Indicator 2 is flashing Channel 2
is displayed. Pulse alarm in channel
2 *)
Header piping is leaking.
Locate and repair the leakage.
There is air in the pumping unit or
the header piping.
Remove air from the pumping unit or
the header piping. Reset the alarm.
Check the suitability of the lubricant
from the equipment manufacturer.
The distributor is stuck.
Verify which distributor is affected and
replace the distributor.
The pulse sensor is faulty.
Replace the pulse sensor.
The pulse sensor cable is
damaged.
Repair or replace the cable.
Malfunction in the SKF Multilube
pumping centre.
Locate and repair the malfunction or
contact the equipment supplier.
Indicator 1 is lit and P is flashing.
Channel 1 is displayed. Reservoir
low level alarm
Indicator 2 is lit and P is flashing.
Channel 2 is displayed. Reservoir
low level alarm
Lubricant reservoir is empty.
Fill the lubricant reservoir.
Reset the alarm.
*) Pulses received from the pulse sensors are displayed as short, 50 millisecond flashes, the pulse sensor of channel 1 in
indicator 1 and the pulse sensor of channel 2 in indicator 2.