SKIPPER website (www.skipper.no) and may be downloaded and the system
upgraded using a PC connected to the ’Compact’ COM port in the electronic
unit (JB60CD). Alternatively a chip can be supplied (with an additional cost)
with the new software. This is changed by removing the backplate of the
display unit.
To upgrade the software, select which com port is to be used (for JB60CD
electronic unit ’Compact’ DSUB use ’COMPACT’ port, and select SENSR for
upgrade). Ensure the line is clear by removing power from the EML sensor.
Press set and restart the system. The unit will wait for new rmware for two
minutes. After that it will start with the existing code. You may then start the
SKIPPER service software (downloadable from the SKIPPER website), select
the Compact display window, and then use the upgrade button to upgrade the
unit.
MASTER RESET (FACTORY DEFAULT SETTINGS)
The factory default settings can be restored by performing the following
operations:
1. Select CODE in diagnostic (DIAG) menu.
2. Press the SET button (Note: Do not change code value, just press the SET
button.)
The unit will now restart with factory default settings.
Note. On Compact speed log systems, this will also reset the stored
calibration values. We therefore recommend to write down the values before
attempting this.