46 User Manual
DOL 534 • DOL 539
3.7.5 Inlet De-ice
This section is relevant only for houses with de-ice for air inlet.
Climate/ Ventilation/ Inlet de-ice
De-icing is a function, which changes the regulation of the ventilation to Cycle time at low temperatures to
prevent ice formation in the air inlets.
DOL 53X activates de-icing when the outside temperature falls below the setting for Outside temperature
below.
Example 15: Activation of de-icing
ON
Outside temperature
below
-10 °C
OFF
Outside temperature °C
You must set Outside temperature below to the number of degrees to which the outside temperature can fall before
DOL 53X activates the de-icing function.
-10 0-8 10
De-icing disconnects again