74 User Manual
DOL 534 • DOL 539
4.6 Catching
Catching is designed to change the air change in the house in the event that the animals or a part of them are to
be taken out the house. The ventilation status will change to Catching and adapt its settings. When it changes
back, the ventilation returns to half the ventilation requirement that was just before the function started. The
function also amends the feed program, lighting control and alarm.
Catching can be set up to activate in two ways:
- External key
- Display Operation
Setting the date and time that the DOL 53X can activate the function.
Setting the period when DOL 53X can activate the function. If you forget to end
the catching function, the DOL 53X provides an alarm when this time is exceeded.
Connection and disconnection of the function.
Setting the maximum period that Catching can be active.
Displaying the time when Catching was activated. Only visible when the function
is active.
Displaying the time when the function is to stop (using the Maximum active time).
If the catching takes a longer than expected, then the stop time can be changed.
Only visible when the function is active.
Setting how much the air inlets must be open in percent.
Setting how much the air inlets must be open in percent.
Selecting which MultiStep should be active during Catching.
For example, you can control the desired direction of the airflow, by only
activating the MultiSteps at one end of the house.
Selection of whether activation of Catching will stop the feeding system.
Stop feed weigher
before feed system
is stopped
Setting the time period. The time period should correspond to the time it takes for
the animals to eat the feed which is distributed in the system.
Stop feed mix
before feed
weigher is
stopped
Setting the time period. The time period should correspond to the time that the
animals should only have one type of feed.