User Manual 49
DOL 534 • DOL 539
Example 16: Cooling
Cooling %
Temp. setpoint incl.
additions
24° C
Start cooling
2.5° C
Temperature °C
A prerequisite for cooling to be able to start however is that ventilation is set to Maximum ventilation or that the
outside temperature is over Temperature setpoint.
DOL 53X gradually increases cooling.
3.8.1 Nozzle Cleaning
To clean the nozzles, DOL 53X can activate side cooling independently of the house's cooling requirement.
Nozzle cleaning
active
Connection and disconnection of nozzle cleaning.
Nozzle cleaning
time
Setting of the time that must elapse from when side cooling was last active to when
the nozzle cleaning function will run.
Nozzle cleaning
interval
Setpoint of the time when side cleaning shall operate.
Temp. setpoint incl. additions
Start cooling