5.4.1.3 Emergency Air Intake
This section is relevant only to houses where emergency air intake is
installed.
The emergency air intake can be generated by four types of alarms.
Emergency inlet
Activated by
Emergency inlet (Temperature)
Set
Abs. high temperature
Connect or disconnect
Error inside temp. sensors
Connect or disconnect
Power failure
Always activate
Table 16: Activation of emergency air intake
Whether a faulty inside temperature sensor should activate the emergency air intake depends on the general
climate conditions. If it is very hot, you could profit from using the function. However, if it is cold, you should
consider the necessity of using it and whether the animals will suffer.
Emergency air intake has its own temperature setting, Emergency air intake, which constitutes a number of
degrees to be added to Temperature setpoint and possibly Comfort temperature.
This setting makes it possible to open the air intake during a hot season where the air intake, under normal
conditions, is not activated by the normal high temperature alarm limit.
5.4.1.4 Power Failure Alarm
The DOL 53X controller will always generate an alarm in case of power failure.