Messages SMA Solar Technology AG
70 SB20_25_30HF-IEN102911 Installation Guide
6< Grid fault >
The internal inverter monitoring has
detected an impermissibly high proportion
of direct current in the grid current.
• Check the grid connection for direct
current.
• If this is a recurrent phenomenon,
check with the utility provider
whether it is possible to raise the
limiting value of monitoring.
7 < Frq. not permitted >
The grid frequency has left the allowable
range. For safety reasons, the inverter
disconnects itself from the grid.
• If possible, check the grid frequency
and observe how often major
deviations occur.
If repeated frequency variations occur and
as a result this error occurs, ask the utility
provider if it would agree to modify the
operating parameter.
Discuss the proposed parameters with the
SMAServiceline.
8 < Waiting for grid voltage >
< Grid failure >
< Check fuse >
•Check fuse.
• Check AC installation.
• Check whether there is a general
black-out.
33 < Unstable operation >
The supply at the DC input of the inverter is
not sufficient for stable operation. The
reason for this could be snow-covered
PVmodules.
• Wait for higher irradiation.
• If this event recurs at medium
irradiation, check the PV system
design and correct the connection of
the PV generator.
34 < DC overvoltage >
< Disconnect generator >
The DC input voltage connected to the
inverter is too high.
• Immediately disconnect the
inverter from the PV generator,
as described in section
8.2”Disconnect the Inverter
from Voltage Sources”
(page60)! Otherwise, the
inverter may be destroyed.
• Check the DC voltage of the strings
for adherence to the maximum input
voltage of the inverter, before you
re‑connect the inverter to the
PVgenerator.
Event no. Display message and cause Corrective measures