5 Mounting SMA America, LLC
26 SB30-40-US-IA-en-33 Installation Manual
5.2 Selecting the Mounting Location
Requirements for the mounting location:
The mounting must be on a stable surface, e.g. concrete and other walls.
The mounting location must be suitable for the weight and dimensions of the inverter
(see Section 12 "Technical Data", page 90).
In living areas, make sure that the mounting surface is not made of plasterboard or similar.
The inverter makes noises when in use, which can be perceived as a nuisance in a living area.
Studs must be present behind the mounting points on plasterboard sheets or panels.
The mounting location must be clear and have safe access at all times without the use of
additional aids being necessary (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
The mounting location must not be exposed to direct solar irradiation. Direct solar irradiation
can overheat the inverter. As a result, the inverter reduces its power output.
The mounting location must not be exposed to direct sources of water spray such as sprinklers
or gutters.
The ambient temperature must be within a permissible range (see Section 12 "Technical
Data", page 90). This ensures optimal operation of the inverter.
The mounting location must be inaccessible to children.
Danger to life due to fire or explosions
With electrical devices, there is always a certain danger that a fire may break out.
Do not mount the inverter in the vicinity of combustible materials.
Do not mount the inverter in areas where highly flammable materials are stored.
Do not mount the inverter in a potentially explosive atmosphere.