SMA America, LLC 6 Electrical Connection
Installation Manual SB30-40-US-IA-en-33 39
6.3 AC Connection
6.3.1 Inserting the AC Cables into the DC Disconnect
Additional required mounting material (not included in the scope of delivery):
1 rain-tight or water-tight sleeve (
3
4
in. (19 mm)).
1 rigid conduit (
3
4
in. (19 mm)).
Cable requirements:
The AC cables must be designed for ambient temperatures exceeding +194°F (+90°C).
The maximum cable length, which is dependent on the conductor cross-Section, must be
adhered to.
Conductor material: Copper wire
Conductor cross-Section: AWG 10 to 6 AWG (6 mm
2
to 16 mm
2
)
The AC cables must be designed according to the installation requirements applicable on site.
Requirement:
The AC cables must be protected using a switch-disconnector or miniature circuit-breaker
(see National Electrical Code
®
, ANSI/NFPA 70). For this purpose, observe the maximum
permissible fuse protection of 30 A.
All electrical installations must be carried out according to all electrical standards applicable on
site and the National Electrical Code
®
(NE, ANSI/NFPA 70).
Installations in Canada must be carried out in accordance with the applicable Canadian
standards.
1. Disconnect the AC miniature circuit-breaker and ensure that it cannot be reconnected.
2. Open the DC Disconnect (see Section 9.3).
3. Break out a suitable knockout on the underside of the DC Disconnect for inserting the AC cable.
5. Insert 1 rain-tight or water-tight sleeve (
3
4
in. (19 mm)) in the enclosure opening of the
DC Disconnect and tighten from the inside using a counter nut.
6. Install 1 rigid conduit (
3
4
in. (19 mm)) in the enclosure opening.
7. Insert the AC cables of the power distribution grid into the interior of the DC Disconnect through
a rigid conduit.
4.
Damage to the DC Disconnect due to penetration of moisture
Electronic components in the inverter can be destroyed or damaged as a result of moisture
penetration.
Only break out 1 knockout for the connection of the AC cable.
Do not enlarge the enclosure opening.