HIGH BALANCE POINT SELECTION USING OUTDOOR SENSOR
Menu 19:HB allows you to select a high balance point setting when the
thermostat is configured for Fossil Fuel. When the outdoor temperature rises
above the balance point setting, the furnace is locked out and only the
compressor is used for heating. The factory default is OFF. Touch the UP and
DOWN arrows to change the setting. Setting can be from 0° to 50° C.
INSTALLER SETUP MENU
E
44