MGC300 Genset Controller User Manual
MGC300 Genset Controller Version 1.1 2020-01-04 Page 12 of 27
4.4.4 AUTO STOP SEQUENCE
a. When remote start input is invalid, “Stop Delay” time is initiated;
b. Once this “stop delay” has expired, the “Cooling Down Delay” is then initiated;
c. When “Stop Idle Delay” (if configured) starts, idle speed relay is energized and outputs;
d. When “ETS Solenoid Hold” begins, ignition control relay is energized and fuel relay is de-energized;
e. When controller enters "Wait for stop" time, it will judge whether genset has stopped completely;
f. After complete stop, controller will enter standby status; if genset cannot stop controller will issue
alarm (LCD displays ).
NOTE 3: Press stop key in auto start status, generator will stop and enter into stop mode simultaneously.
NOTE 4: In the procedure of crank rest time, when fuel output is disconnected and crank rest countdown is less than 7s,
preheating and ETS stop output; after crank rest time, ETS stop output is disconnected and fuel outputs; Preheating is
stopped before crank.
4.4.5 MANUAL START/STOP OPERATION
Manual Start: press to start genset (Please refer to start procedure b~g of AUTO START
SEQUENCE). If water temp. high, over speed, and abnormal voltage occur during the running process,
controller shall protect it to stop quickly.
Manual Stop: press to stop the running genset (Please refer to stop procedure b~f of AUTO
STOP SEQUENCE).