4.2 PUSH BUTTONS
Table 3 Button Description
Stop the running genset both in manual mode and in auto mode;
In alarm status, press this button to reset any shutdown alarms.
In stop mode, press this button and Up key to test if LCD icons and LED
indicators are OK.
In stop mode, press this button and Down to set backlight always on;
In stop process, re-press this button to stop generator immediately.
In parameter setting process, press this button to exit the setting quckly;
In stop status, press this button to start;
In start status, press longer for 3s and release to stop the genset;
Press this key and controller enters to Auto mode; under this mode, genset
can be controlled by remote start input signals;
Press this key and genset will start;
LCD page scroll;
In parameter settings, decrease the value where
the cursor is;
Press the two keys
simultaneously to enter
parameter settings
page;
LCD page scroll;
In parameter settings, increase the value where
the cursor is;
Confirm key for parameter settings page;
Manual key for other pages and press it to make controller in Manual mode;
This key is especially for MGC310;
Confirm key for parameter settings page;
Test key for other pages and press it to make controller commissoning;
This key is especially for MGC320;