MGC300 Genset Controller User Manual
MGC300 Genset Controller Version 1.1 2020-01-04 Page 13 of 27
5 PROTECTION
Table 5 Alarm Types
Icons
Alarm Contents
Type
Trigger
Over Frequency Stop
Shutdown
Gen frequency is above over frequency limit for 2s, it
will issue alarm;
Under Frequency Stop
Shutdown
Detected when genset is running normal; gen freq. is
less than under frequency limit for 10s, and it alarms.
Temp. High
Shutdown
Detected after safety on delay; when temp. high is
above high temp. limit for 3s, it will issue alarm;
Temp. High Input
Shutdown
Detected after safety on delay; when temp. high input is
active, it will issue alarm;
Oil Pressure Low Input
Shutdown
Detected after safety on delay; it alarms when oil
pressure low input is active;
Gen Over Current
Warning
Action is set to Warning; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Gen Over Current
Shutdown
Action is set to Shutdown; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Gen Over Current
Cooling Shutdown
Shutdown
Action is set to Cooling Shutdown; gen current is over
pre-set value and lasting time is over delay, it alarms;
Gen Voltage High
Shutdown
Detected after safety on delay; gen voltage is over the
threshold, and this lasts for over delay, and it alarms;
Gen Voltage Low
Shutdown
Detected after genset running; gen voltage is lower
than threshold for over the delay time, and it alarms;
Fail to Crank
Shutdown
It alarms when starter doesn't start the engine in the
range of the pre-set start times;
Outside Shutdown
Alarm Input
Shutdown
When "outside shutdown alarm" is configured for the
input port, and when the input is active, it alarms;
Fuel Level Low
Warning
When fuel level is lower than the threshold for 10s, it
alarms;
Fuel Level Low Input
Warning
When fuel level low input is active, it alarms;
Fail to Stop
Warning
Complete stop time is over but genset still stops
completely and controller will alarm;
Battery Voltage Low
Warning
Battery voltage is lower than the threshold for 20s, it
alarms;
Battery Voltage High
Warning
Battery voltage is higher than the threshold for 20s, it
alarms;
NOTE 1: Shutdown alarms are latched signals and alarms can be removed by using Stop key (in stop status); warning
alarms are not latched.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen GENSET CONTROLLER MGC310 and is the answer not in the manual?

Smartgen GENSET CONTROLLER MGC310 Specifications

General IconGeneral
BrandSmartgen
ModelGENSET CONTROLLER MGC310
CategoryController
LanguageEnglish

Related product manuals