HGM6100K Series Automatic Generator Module
HGM6100K Series Automatic Generator Module ISSUE 2011-04-12 Version 1.6 Page 16 of 31
When the engine speed is
over than the point and
hold great than 2 seconds,
generator over speed is
active.
When generator freq. is
low than the point,
generator low frequency
and hold great than 10
seconds is active.
When generator freq. is
over than the point and
hold great than 2 seconds,
generator over frequency
is active.
When engine temperature
sensor value is over than
this point and remain for 2
seconds, send out
shutdown alarm. When the
value is 140, send out
warning alarm. (It‟s suited
for engine temperature
sensor only).
When engine oil pressure
sensor value is under than
this point and remain for 2
seconds, send out
shutdown alarm. When the
value is zero, send out
warning alarm. (it‟s suited
for oil pressure sensor
only)
When fuel level sensor
value is under than this
point and remain for 10
seconds, send out warning
alarm.