3 SPECIFICATION
Items Contents
Working Voltage DC8.0V to DC35.0V, continuous
Power Consumption <3W(Standby mode: ≤2W)
AC System
3P4W
3P3W
1P2W
2P3W
AC15V - AC360 V (ph-N)
AC30V - AC620 V (ph-ph)
AC15V - AC360 V (ph-N)
AC15V - AC360 V (ph-N)
AC Alternator Frequency 50Hz/60Hz
Rotate speed sensor Voltage 1.0V to 24V (RMS)
Rotate speed sensor Frequency 10,000 Hz (max.)
Start Relay Output 16 A DC28V at supply voltage
Fuel Relay Output 16 A DC28V at supply voltage
Programmable Relay Output 1 7 A DC28V at supply voltage
Programmable Relay Output 2 7 A 250VAC volt-free output
Programmable Relay Output 3 16 Amp 250VAC volt-free output
Programmable Relay Output 4 16 A 250VAC volt-free output
Overall Dimensions 197 mm x 152 mm x 47mm
Panel Cutout 186mm x 141mm
C.T. Secondary Current 5A (rated)
Working Condition Temperature: (-25~70C; Humidity: (20~93)%
Storage Condition Temperature: (-25~+70)ºC
Protection Level IP55 Gasket
Insulation Intensity
Apply AC2.2kV voltage between high voltage
terminal and low voltage terminal;
The leakage current is not more than 3mA within
1min.
Weight 0.56kg