HGM7220N/HGM7220S GENSET CONTROLLER USER MANUAL
HGM7220N/HGM7220S Genset Controller 2019-02-28 Version 1.0 Page 16 of 60
6 PROTECTION
6.1 WARNINGS
When controller detects the warning alarms, it only issues alarm and does not stop the genset.
Table 5 - Warning Alarm Types
No.
Type
Description
1
Gen. Over Speed
When the controller detects that the genset speed exceeds the pre-set
limit, it will initiate a warning alarm.
2
Gen. Under Speed
When the controller detects that the genset speed falls below the
pre-set limit, it will initiate a warning alarm.
3
Loss of Speed Signal
When the controller detects that the speed of genset is zero and action
is selected Warning”, it will initiate a warning alarm.
4
Gen. Over Frequency
When the controller detects that the frequency of genset exceeds the
pre-set limit, it will initiate a warning alarm.
5
Gen. Under Frequency
When the controller detects that the frequency of genset falls below
the pre-set limit, it will initiate a warning alarm.
6
Gen. Over Voltage
When the controller detects that the voltage of genset exceeds the
pre-set limit, it will initiate a warning alarm.
7
Gen. Under Voltage
When the controller detects that the voltage of genset falls below the
pre-set limit, it will initiate a warning alarm.
8
Gen. Over Current
When the controller detects that the current of genset exceeds the
pre-set limit, it will initiate a warning alarm.
9
Failed to Stop
If engine does not stop completely when failed to stop delay is
expired, it will initiate a warning alarm.
10
Charge Alt Fail
When the controller detects that the voltage of charger falls below the
pre-set limit, it will initiate a warning alarm.
11
Battery High Voltage
When the controller detects that the battery voltage of genset exceeds
the pre-set limit, it will initiate a warning alarm.
12
Battery Low Voltage
When the controller detects that the battery voltage of genset falls
below the pre-set limit, it will initiate a warning alarm.
13
Maintenance Time Due
When maintenance countdown is zero and action is selected
Warning, it will initiate a warning alarm.
14
Reverse Power
When controller detects that the reverse power value (power is
negative) of genset exceeds the pre-set limit, and action is selected
Warning, it will initiate a warning alarm.
15
Over Power
When controller detects that the power value (power is positive) of
genset exceeds the pre-set limit, and action is selected Warning, it
will initiate a warning alarm.
16
ECU Warn
When controller receives engine warning signal via J1939, it initiate a
warning signal.
17
Gen. Loss of Phase
When controller detects that the phase of generator is lost, it will
initiate a warning alarm.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen HGM7220N Series and is the answer not in the manual?

Smartgen HGM7220N Series Specifications

General IconGeneral
BrandSmartgen
ModelHGM7220N Series
CategoryController
LanguageEnglish

Related product manuals