MGC100 Petrol Genset Controller User Manual Page 14 of 16
8 PARAMETERS SETTING
8.1 PARAMETERS REGULATION
When the controller is running, press for 3s, it will enter into parameter number menu and LED
will display :
1) Press and to downturn/upturn parameter number;
2) After parameter number is selected, press to enter into parameter setting menu; press
and to increase/decrease parameter value (it can be double-clicked);
3) Press to confirm modification and save value;
4) For multiple parameters, step (1-3) can be repeat done for setting;
5) After parameter setting, press for 3s to exit parameter setting status.
8.2 RESTORE FACTORY SETTINGS
In emergency stop input status, press and for 5s at the same time, it can restore to
default and “reset” will be displayed on LED.
8.3 ELIMINATE ACCUMULATED TIME
Press and for 5s at the same time, accumulated running time will be reset an “hclr” will
be displayed on LED.
NOTE:
——Over voltage threshold must be greater than under voltage threshold.
——When start successfully, generator frequency need to be set lower as soon as possible in order to starter
separate sooner.
——Number of setting contents refers to Parameter Content and Range (Table 7)”.
——Only in parameter number menu can exit from parameter setting status. If there is no press operation in
parameter number menu, it will exit in 30s automatically.