26
http://support.weathermatic.com
Troubleshooting 7.0
PROBLEM CAUSES SOLUTIONS
SmartLine® controller does
not turn on zone when
expected
Sensor jumper is removed and no
sensor is connected (Sensor LED
is red)
Install jumper wire between SEN terminals
Select OFF mode if desired
Sensor wires have been cut
(Sensor LED is red)
Repair wires
Zone comes on at unexpected
time
Program daily start times not set properly or multiple start times set.
Check Program Start Times
Stacked program has
commenced normal operation
Modify settings (such as program start times, zone run times) to
prevent stacking if undesirable
Time of day or date not set
properly
Review/set time of day and date
Watering days or omit days/dates
not set properly
Review/set watering days or omit days/dates
Run/Soak feature has extended
watering window
Normal operation to allow water infiltration and prevent runo
Controller does not operate zone
for expected run time
Pause for Run/Soak in progress. This is normal operation to allow
water infiltration and prevent runo
Check seasonal % settings if BASIC mode is in use.
Module not installed Install module
No initial AC power-up of
controller
Connect AC power and close control panel