ENGLISH
IOMMASGPXX01-GB_01
57
10-40 kVA
10
OPTIONS
10.8.1 Protection on Mains Supply and on Auxiliary Mains Supply.
Activating UPS protection on the mimic panel: access the Conguration menu on the mimic panel (see the Con-
guration Menu section in the manual) and set the BACKFEED TYPE parameter to 2.BYPASS-INPUT Alone.
Diagram of principle.
Legend.
A Distribution panel
B Coil remote switch
L1-L2-L3-N Input power source
L11-L21-L31-N1 Backup power source
M1 Input power terminal board
M2 Backup power terminal board
T1 Remote switch
1
T2 Remote switch
1
Q1 Input power switch
Q2 Backup power switch
XB1 Connector on BKF PCB
XB2 Connector on BKF PCB
10.8.1-1
A UPS
L11
Q2
L21
L31
N1
T2
B
M2
L11
L21
L31
N1
XB1
XB2
BKF card
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
UPS 3/3 with separate auxiliary supply.
10.8.1-2
A UPS
Q2
L11
N1
T2
B
M2
L11
N1
XB1
XB2
BKF card
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
UPS 3/1 with separate auxiliary supply.
1
Remote switches - rated current
Model T1 T2
10 3/1 32 A AC1 45 A AC1
15 3/1 32 A AC1 45 A AC1
20 3/1 45 A AC1 60 A AC1
10 3/3 32 A AC1 32 A AC1
15 3/3 32 A AC1 32 A AC1
20 3/3 45 A AC1 45 A AC1
30 3/3 60 A AC1 60 A AC1
40 3/3 90 A AC1 90 A AC1