10-40 kVA
OPTIONS
10
10.8.2 Protection on an UPS without auxilary mains supply.
Activating UPS protection on the mimic panel: access the Conguration menu on the mimic panel (see the Congu-
ration Menu section in the manual) and set the BACKFEED TYPE parameter to 3.BYPASS-INPUT Common.
Attention.
The neutral on the input or the output of the UPS are identical. Consequently there is no risk of high potential when
the input power supply is absent.
However, depending on the type of system connected in the output or in some failure conditions (earth leakage,
signicant phase dispersion or in case of non-isolated neutral system), high potential can be detected. It will there-
fore be necessary to install either adequate neutral switching or protection system.
10.8.2-1
A UPS
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
XB1
BKF card
UPS 3/3 without separate auxiliary supply.
Legend.
A Distribution panel
B Coil remote switch
L1-L2-L3-N Input power source
M1 Input power terminal board
Q1 Input power switch
T1 Remote switch
1
XB1 Connector on BKF PCB
1
Remote switches - rated current
Model T1
10 3/1 32 A AC1
15 3/1 32 A AC1
20 3/1 45 A AC1
10 3/3 32 A AC1
15 3/3 32 A AC1
20 3/3 45 A AC1
30 3/3 60 A AC1
40 3/3 90 A AC1
Diagram of principle.