NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
101
EN
Model RT-5K RT-7K RT-9K RT-11K
Display LED indicators and LCD display
Communication
Interfaces
SMART Slot × 1, RS-232 Port × 1, USB Port × 1,
Parallel Port x 2, REPO/ROO × 1, RS-485 Port × 1,
Dry Contact × 4 (Out: 250V 8A resistive load)
Physical
Dimensions
(W × D × H)
440 × 430/ 508*
3
× 89 mm
(17.3 × 16.9/ 20 × 3.5 inch)
440 × 565/ 643*
3
× 89 mm
(17.3 × 22.2/ 25.3 × 3.5 inch)
Weight
11 kg
(24.2 lb)
12 kg
(26.4 lb)
16 kg
(35.2 lb)
17 kg
(37.5 lb)
Environ-
ment
Operating
Altitude
0 ~ 3000 m (0 ~ 10000 ft);
0 ~ 1000 m (0 ~ 3300 ft) (without derating)
Operating
Temperature
0°C ~ 55°C*
4
(32 ~ 131°F)
Storage
Temperature
-15°C ~ 55°C (-59 ~ 131°F)
Relative
Humidity
5% ~ 95% (non-condensing)
Standard Compliance
CE / TUV GS / EN IEC 62040-1,
EN IEC 62040-2, Category C2
*
1
: In free running mode the UPS needs to be de-rated to 70% of its capacity.
*
2
: The UPS needs to be de-rated to 70% of its capacity.
*
3
: The latter value of UPS depth is measured including its terminal block.
*
4
: When the operating temperature is at 40 ~ 55°C (104 ~ 131°F), the UPS
will be de-rated to 75% of its capacity.
Please refer to the rating label for the safety rating.
All specications are subject to change without prior notice.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec NETYS RT 5000 and is the answer not in the manual?

socomec NETYS RT 5000 Specifications

General IconGeneral
Brandsocomec
ModelNETYS RT 5000
CategoryUPS
LanguageEnglish

Related product manuals