EasyManuals Logo

socomec NETYS RT 5000 User Manual

socomec NETYS RT 5000
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
42
EN
Backfeed Protection Device Requirements:
set the DRY contact with «backfeed» conguration.
UPS
Suggested Backfeed
Protection Device
Rating Voltage/ Current
5 / 7 kVA 208/ 220/ 230/ 240Vac; 40A
9 / 11 kVA 208/ 220/ 230/ 240Vac; 65A
Backfeed Protection Wiring Diagram:
Please refer to the diagram below to install the backfeed protection device
between the AC input and the UPS.
DC 12V
L
N
L
N
L
N
UPS
Dry
Contact
Contactor
Control relay
(Figure 7-2: Backfeed Protection Wiring Diagram)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec NETYS RT 5000 and is the answer not in the manual?

socomec NETYS RT 5000 Specifications

General IconGeneral
Brandsocomec
ModelNETYS RT 5000
CategoryUPS
LanguageEnglish

Related product manuals