NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
54
EN
Output
Setup Items Selectable Value Default
Output Phase 1-phase 1-phase
Output Voltage
200V, 208V, 220V,
230V, 240V
230V
Output Frequency
Auto*
1
/ Converter-50Hz*
2
/
Converter-60Hz*
2
Auto
Output Sync.
Freq. Range
±0.5/ 1/ 3/ 5Hz ±3Hz
Output Freq.
Slew Rate
0.5 / 1 / 2Hz/sec. 1 Hz/sec.
Output Mode Industrial/ IT IT
Standby Mode No output/ Bypass output No output
Overload Alarm 30-105% (per step: 5%) 105%
*
1
: When the Output Frequency is set as Auto, the output frequency will
vary according to the bypass frequency. If the bypass frequency is ≥ 55Hz,
the Free_Run_Frequency/ Cold_Start_Frequency will be set as 60Hz.
If the bypass frequency is < 55Hz, the Free_Run_Frequency/ Cold_Start_
Frequency will be set as 50Hz.
When the Output Frequency is set as Auto and the Bypass Output
under the Standby Mode item is set as Enable, the bypass output range
will be the same as the Output Sync. Freq. Range.
*
2
: When the Output Frequency is set as Converter-50Hz/ Converter-
60Hz, the UPS will enter the Frequency Conversion mode and the bypass
output will become Disable.
Input
Setup Item Selectable Value Default Value
Bypass Max. Voltage +10/ 15/ 20% +15%
Bypass Min. Voltage -10/ 15/ 20/ 25/ 30/ 35/ 40% -20%