NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
86
EN
10.3.2. Important Safety Instructions
Safety Instructions
The two gures below indicate that there is high voltage circuit inside. Do not
open the cover of the lithium-ion battery pack.
• The operation temperature for Li-ion battery EBC is 0-45’C.
• The UPS will shut down if the temperature goes up to 80°C when discharging
and it will restart automatically when utility recover. The EBC will resume when
the temperature is below 60°C.
• Please not that the battery will stop charging when the temperature reaches
50°C and will resume charging when the temperature is below 50°C. During this
time, the UPS can run as usual.
Standard Compliance
• CE
• CAN/ UL1973
Storage
• Prior to installation
If the lithium-ion battery pack needs to be stored prior to installation, it should be
placed in a dry area. The allowable storage temperature and relative humidity (non-
condensing) are -15°C ~ +50°C (5°F ~ 122°F) and 5 ~ 95% respectively.
• After usage
Remove all connected devices from the lithium-ion battery pack, and store the
lithium-ion battery pack in a dry and well-ventilated area at a temperature between
-15°C and +50°C (5°F ~ 122°F) and at a relative humidity (non-condensing)
between 5 ~ 95%.
Recycling and Disposal
• Please follow the local and/or national regulations when recycling or disposing of
the lithium-ion battery pack.

Questions and Answers: