13.4 Individual country settings
Parameter Unit Germany Spain
≤ 13.8kVA > 13.8kVA > 30kVA
VDE
0126-1-1
Medium
voltage
Vac min 1 V 184 184 0 184 184 196
t Vac min 1 ms 200 200 0 200 2000 1500
Vac max 1 V 264 264 0 264 264 253
t Vac max 1 ms 200 200 0 200 100 1500
Vac min 2 V 0 0 0 0 104 0
t Vac min 2 ms 0 0 0 0 1500 0
Vac max 2 V 0 0 0 0 0 264
t Vac max 2 ms 0 0 0 0 0 200
Vac 10 min max V 253 253 0 253 0 0
Monit. ext. input On/Off - - Off - - -
f min 1 Hz 47.5 47.5 0 47.5 47.5 48
t f min 1 ms 200 200 0 200 100 3000
f max 1 Hz 51.5 51.5 0 51.5 51.5 50.5
t f max 1 ms 200 200 0 200 100 500
f min 2 Hz 0 0 0 0 0 0
t f min 2 ms 0 0 0 0 0 0
f max 2 Hz 0 0 0 0 0 0
t f max 2 ms 0 0 0 0 0 0
df/dt max Hz/s 0 0 0 0 0 0
Ierr max mA 300 300 300 300 300 300
Iac mean max mA 1000 1000 1000 1000 1000 0.5% of
Iacmax
Restart delay s 0 0 0 0 0 0
Mains check On/Off On On Off On On On
- Vac MC max V 253 253 280 253 280 264
- Vac MC min V 196 196 161 184 219 196
- f MC max Hz 50.05 50.05 55 50.2 50.05 50.5
- f MC min Hz 47.5 47.5 45 47.5 47.5 48
- t MC monitoring s 60 60 0 30 0 180
Island Detection On/Off On On On On Off On
Soft Start W/s 0 0 0 0 0 0
Pac progression %/min 10 10 10 0 0 0
P(f)-Mode On/Off On On On On On -
- f start Hz 50.2 50.2 50.2 50.2 50.2 -
- f stop Hz - - - - 50.05 -
- Reduction %/Hz 40 40 40 40 40 -
- Re-increase %/min 10 10 10 10 - -
Q-Mode
cos(φ)(Pac) cos(φ)(Pac) cos(φ)(Pac)
Off Off Off
- Vac Lock On/Off - - - - - -
- Vac Lock-In V - - - - - -
- Vac Lock-Out V - - - - - -
FRT On/Off - - - - On -
- K factor - - - - 2.0 -
S max SM8MT2 VA 8000 8000 8000 8000 8000 8000
S max SM10MT2 VA 10000 10000 10000 10000 10000 10000
S max SM13MT2/3 VA 13000 13000 13000 13000 13000 13000
S max SM15MT2/3 VA 15000 15000 15000 15000 15000 15000
Pac max SM8MT2 W 8000 8000 8000 8000 8000 8000