113
Parameter Unit Greece Greece Portugal Great
Britain
Switzerland Bulgaria
Mainland Islands
- t MC monitoring s 180 180 20 180 30 30
Island Detection On/Off On On On On On On
Soft Start W/s 0 0 0 0 0 0
Pac progression %/min 0 0 0 0 0 0
P(f)-Mode On/Off - - - - - -
- f start Hz - - - - - -
- f stop Hz - - - - - -
- Reduction %/Hz - - - - - -
- Re-increase %/min - - - - - -
Q-Mode Off Off Off Off Off Off
- Vac Lock On/Off - - - - - -
- Vac Lock-In V - - - - - -
- Vac Lock-Out V - - - - - -
FRT On/Off - - - - - -
- K factor - - - - - -
S max SM8MT2 VA 8000 8000 8000 8000 8000 8000
S max SM10MT2 VA 10000 10000 10000 10000 10000 10000
S max SM13MT2/3 VA 13000 13000 13000 13000 13000 13000
S max SM15MT2/3 VA 15000 15000 15000 15000 15000 15000
Pac max SM8MT2 W 8000 8000 8000 8000 8000 8000
Pac max SM10MT2 W 10000 10000 10000 10000 10000 10000
Pac max SM13MT2/3 W 13000 13000 13000 13000 13000 13000
Pac max SM15MT2/3 W 15000 15000 15000 15000 15000 15000
Iac max SM8MT2 A 12 12 12 12 12 12
Iac max SM10MT2 A 16 16 16 16 16 16
Iac max SM13MT2/3 A 20 20 20 20 20 20
Iac max SM15MT2/3 A 22 22 22 22 22 22
Parameter Unit Romania Hungary Turkey China Israel Australia
Vac min 1 V 184 184 184 196 207 207
t Vac min 1 ms 200 200 200 2000 2000 2000
Vac max 1 V 264 264 264 253 264 264
t Vac max 1 ms 200 200 200 2000 2000 2000
Vac min 2 V 0 0 0 115 0 0
t Vac min 2 ms 0 0 0 100 0 0
Vac max 2 V 0 0 0 0 0 0
t Vac max 2 ms 0 0 0 0 0 0
Vac 10 min max V 253 253 253 0 0 0
Monit. ext. input On/Off - - - - - -
f min 1 Hz 47.5 47.5 47.5 49.5 45.5 45.5
t f min 1 ms 200 200 200 600500 2000 2000
f max 1 Hz 50.2 50.2 50.2 50.2 54.5 54.5
t f max 1 ms 200 200 200 120500 2000 2000
f min 2 Hz 0 0 0 48 0 0
t f min 2 ms 0 0 0 200 0 0
f max 2 Hz 0 0 0 50.5 0 0
t f max 2 ms 0 0 0 200 0 0
df/dt max Hz/s 0 0 0 0 0 0
Ierr max mA 300 300 300 300 300 60