22
Menu “Plant type” for country setting “Germany”:
Setting Description
<= 3.68 kVA The maximum plant system rating is 3.68 kVA.
> 3.68 – 13.8kVA The plant system rating is higher than 3.68 kVA and/or is maximally 13.68
kVA.
> 13.8 kVA – 30 kVA The plant system rating is higher than 13.68 kVA and/or is maximally 30 kVA.
> 30kVA The plant system rating is higher than 30 kVA.
VDE 0126-1-1 Required setting if the inverter is commissioned within a PV plant connected
to the grid before 1 January 2012.
Note: The setting "VDE 0126-1-1" is inadmissible for PV plants connected to
the grid after 31 December 2011.
Press to con rm your entry.
With the “VDE 0126-1-1” setting, the “Con rmation” menu appears afterwards
(step 4).
In the settings for the plant system rating, the “cosφ(P)” menu appears afterwards
(step 3).
Menu “Standard” for country setting “Great Britain”.
Setting Description
G83/1-1 Inverter settings according to standard G83/1-1
G83/2 Inverter settings according to standard G83/2 (available only for SM2000S,
SM3000S and SM4200S)
G59/2 Inverter settings according to standard G59/2 (available only for SM4200S
and SM6000S)
Press to con rm your entry. The “Con rmation” menu appears (step 4).
Menu “Standard” for country setting “Italy”:
Setting Description
DK 5940 Required setting if the inverter is commissioned within a PV plant connected
to the grid before 1 July 2012.
CEI 0-21: <= 3kW The maximum plant system rating is 3 kW.
CEI 0-21: > 3kW – 6kW The plant system rating is higher than 3 kW and/or is maximally 6 kW.
Press to con rm your entry. The “Con rmation” menu appears (step 4).
Step 3: only for country setting “Germany”:
3. In the “cosφ(P)” menu, select the speci cation for the reactive power feed-in required
by the grid operator:
Setting Description
On Standardised reactive power feed-in
Inactive
No reactive power feed-in (cosφ=1)
Press to con rm your entry.
4. In the “Validation” menu, check your entries. You can complete initial start-up after-
wards by pressing
. The main menu will then be displayed (see 6.3.2 Main menu).