52
Efficiency SolarMax 4200S
PAC
[W]
Prelative
[%]
η(250 VDC)
[%]
η(300 VDC)
[%]
η(400 VDC)
[%]
190 5 90.8 91.0 92.8
380 10 93.6 93.8 94.5
760 20 94.6 95.1 95.8
1140 30 94.8 95.4 96.1
1900 50 95.0 95.5 96.2
3800 100 94.4 95.0 95.6
European efficiency 94.6 95.1 95.8
Efficiency SolarMax 6000S
PAC
[W]
Prelative
[%]
η
(250 VDC)
[%]
η(300 VDC)
[%]
η(400 VDC)
[%]
230 5 91.0 92.1 93.4
460 10 94.1 94.5 95.5
920 20 95.1 95.7 96.2
1380 30 95.2 95.8 96.4
2300 50 95.3 95.9 96.5
4600 100 94.5 95.2 96.1
European efficiency 94.9 95.5 96.2
Legend:
P
AC output power [W]
P
relative ratio of output power and rated output [%]
η(VDC) ef ciency at associated input voltage [%]