8 • Technical Data
_____________________________________________________________________________________________
3.2 Rated Currents and Frame Sizes
RVS-DN Model
RVS-DN
FLC
[A]
Frame
Size
Dimensions WxHxD
[mm]
Weight
[Kg]
RVS-DN 8 8 A 153x310x170 4.5
RVS-DN 17 17 A 153x310x170 4.5
RVS-DN 31 31 A 153x310x170 6.0
RVS-DN 44 44 A 153x310x217 7.5
RVS-DN 58 58 A 153x310x217 7.5
RVS-DN 72 72 A 153x310x217 7.5
RVS-DN 85 85 B 274x385x238 14.5
RVS-DN 105 105 B 274x385x238 14.5
RVS-DN 145 145 B 274x385x238 14.5
RVS-DN 170 170 B 274x385x238 14.5
RVS-DN 210 210 C
380x455x292 (1)
32
RVS-DN 310 310 C
380x455x292 (1)
32
RVS-DN 390 390 C
380x455x292 (1)
32
RVS-DN 460 460 D
380x555x292 (1)
39
RVS-DN 580 580 D
470x640x302 (1)
470x655x302 (2)
48
RVS-DN 820 820 D
470x710x302 (1)
470x715x302 (2)
65
RVS-DN 950 950 D
623x660x290 (3)
83.5
RVS-DN 1100 1100 E
723x1100x370 (3)
170
RVS-DN 1400 1400 E
723x1100x370 (3)
170
RVS-DN 1800 1800 E
723x1100x370 (3)
170
RVS-DN 2150 2150 F
750x1300x392 (3)
240
RVS-DN 2400 2400 G
900x1300x410 (3) (4)
350
RVS-DN 2700 2700 G
900x1300x410 (3) (4)
350
RVS-DN 3000 3000 G
900x1300x410 (3) (4)
350
RVS-DN 105 1000V
105 325x400x300
(5)
RVS-DN 170 1000V, 1200V
170 592x500x345
(5)
RVS-DN 210 1000V, 1200V
210 592x500x345
(5)
RVS-DN 310 1000V, 1200V
310 592x500x345
(5)
RVS-DN 390 1000V, 1200V
390 592x500x345
(5)
RVS-DN 460 1000V, 1200V
460 592x500x345
(5)
3.3 RVS-DN Selection
The RVS-DN should be selected in accordance with the criteria of motor current and starting conditions.
3.3.1 Motor Current and Starting Conditions
Select the RVS-DN acco
rding to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the
motor will not be fully loaded).
The RVS-DN is designed to operate under the following maximum conditions:
Ambient
Temperature
[°C]
Starting Current
[A]
Acceleration
Time
[sec]
50 400%xIn 30
Max. starts per hour: 4 starts per hour at maximum ratings and up to 60 starts per hour at light load
applications (consult factory).
Note:
For very frequent starts (inching applications) the inching current should be considered as the Full Load
Current (FLC) (consult factory).
Notes:
(1) – Different dimensions when ordered with UL/cUL/marine approvals.
Refer to section
5.3 page 47 for dimensions when ordered with these approvals.
(2) – Dimensions with preparation for bypass.
(3) – Must be operated with bypass contactor. Add space for current transformers and bus
bars for preparation for bypass.
(4) – Control module is installed separately. Refer to section
5.1.1 page 45 for dimensions.
(5) – Consult factory.
Refer to section
5 on page 34 for detailed dimensions.