Parameter Settings
30
Press Mode
To Advance to
STATISTICAL DATA
-
****
-
Press Select
To store selected parameters, press Store key
LAST STRT PERIOD
NO DATA
Displays last starting time in seconds.
(Time duration until motor’s current reached nominal)
Press Select
LAST START MAX I
NO DATA
Displays the maximum current at last start.
Press Select
TOTAL RUN TIME
0 HOURS
Displays motor’s hour counter since commencement or
since “Statistical Data” was last reset.
Press Select
TOTAL # OF START
0
Displays the total numbers of starts since
commissioning or since “Statistical Data” was last
reset.
Press Select
LAST TRIP
NO DATA
Describes last fault.
Press Select
TRIP CURRENT
0% OF FLA
Displays the current at the last fault.
Press Select
TOTAL # OF TRIPS
0
Displays the total numbers of trips since
commencement or since “statistical Data” was last
reset.
Press Select
PREVIOUS TRIPS – 1…9
PHASE LOSS
Displays historical event of the last 1-9 faults, by
scrolling with the “
” or “” arrows through the
trips stored since commencement or since “Statistical
Data” was last reset.
Press Mode to return to Display Only Mode
% OF MOTOR FLA
Service Mode
Press Mode and keys simultaneously, the LCD
displays:
STORE ENABLE
DEFAULT PARAMET.
Press Store
and
Mode
simultaneously to store factory
Default Parameters. All previously stored parameters
will be erased. This also returns to “Display Only”
Mode.
Or, to Reset Statistical Data:
Press Select
RESET STATISTICS
Press Reset
and
Store
simultaneously to reset all your
statistical data. This also returns automatically to
Statistical Data Mode.
Press Select to see the software program version
Displays program version
PROGRAM VERSION
STRT.DN-020797
Or, for Factory Calibration:
Press Select
Read phase to phase mains voltage.
VOLTAGE ADJUST.
XXX % VOLT
Press Select
Reads current for factory calibration use only.
CURRENT ADJUST.
XX% OF RVS FLC
Press Select
Display goes back to Store Enable Default Parameters
STORE ENABLE
DEFAULT PARAMET.
To exit “Service Mode” press Mode +
simultaneously.
NOTES:
Entering “Service Mode” is possible only
when Stop LED is On.
A Start signal while in “Service Mode” exits
from this mode.