Menu Description
33
MODE
MODE
MODE
MODE
MODE
UPON INITIATION
PARAMETERS DISPLY
PAGE 1 PAGE 2 PAGE 3 PAGE 4
% OF MOTOR FLA MAIN PARAMETERS
START
PARAMETERS
STOP
PARAMETERS
DUAL ADJUSTMENT
PARAMETERS
SELECT
SELECT
SELECT
SELECT
SELECT
TO REVIEW ALL
PARAMETERS
PRESS KEYS TO CHANGE PARAMETER VALUE
When DIP SW# 2 is set ON When DIP SW# 3 is set ON
% OF MOTOR FLA
xx %
CONNECTION TYPE
LINE / INSIDE DELTA
SOFT START CURVE
0 (STANDARD)
SOFT STOP CURVE 0
(STANDARD)
DA: INT. VOLT.
30%
MOTOR INSULATION
52.8 Mohm
STARTER FLC
105 AMP
START TACHO GAIN
O (MIN. GAIN)
STOP TACHO GAIN 0
(MIN. GAIN)
DA: GENERATOR
PARAMETERS
THERMISTOR RES.
3.1 Kohm
MOTOR FLA
105 AMP
SOFT START CURVE
0 (STANDARD)
DEC. TIME
10 SEC.
DA: CUR. LIMIT
400% OF FLA
OPTION CARD
Not Installed
UNDERCURR TRIP
0% OF FLA
SOFT START CURVE
1 !!
FINAL TORQUE
0 (MIN)
DA: ACC. TIME
10 SEC.
UNDERCURR.
DELAY 10 SEC.
SOFT START CURVE
2 !!
STORE ENABLE
STOP PARAMETERS
DA: DEC. TIME
10 SEC.
O/C – SHEAR PIN
850 % OF FLA
SOFT START CURVE
3 !!
DA: MOTOR FLA
105 AMP.
O/C DELAY
0.5 SEC.
SOFT START CURVE
4 (TORQUE)
STORE ENABLE
D. ADJ PARMETERS
OVERLOAD TRIP
115% OF FLA
PULSE TIME
0 SEC.
Note :
Available options
for “Soft-Start Curve”
OVERLOAD DELAY
4 SEC – AT 5 FLA
INITIAL VOLTAGE
30%
UNDELVOLT. TRIP
300 VOLT
INITIAL CURRENT
100-400%
Note : The “Initial Current” starting Curve becomes
available when “Initial Voltage” exceeds 50% ( or 80% )
UNDERVOLT.
DELAY 5 SEC.
CURRENT LIMIT
400% OF FLA
OVERVOLT. TRIP
480 VOLT.
ACC. TIME
10 SEC.
OVERVOLT. DELAY
2 SEC.
MAX. START TIME
30 SEC.
STORE ENABLE
MAIN PARMETERS
NUMBER OF STARTS
10
STARTS PERIOD
30 MIN.
START INHIBIT
15 MIN.
RUN CONTACT DEL.
5 SEC
S
TORE ENABLE START
P
ARAMETERS