3.3 AIR CONSIDERATIONS
The air inlet and outlet are located on the left and right sides
respectively. Restricting airflow into or out of the unit will impair
performance. At least 3 inches of clearance is required on each side
to ensure adequate airflow.
An optional Air Filter is also available (see Section 7 for options).
3.4 COOLANT FILL
The coolant fill cap is located at the top rear of the unit. Twist off
the cap counter-clockwise to open. Fill reservoir to the bottom of the
neck prior to starting unit. Close cap before operating
Recommended Coolants:
Solid State Cooling Systems recommends using Koolance, a pre-
mixed 27% propylene glycol/water based coolant containing an
algaecide and corrosion inhibitors. Though it comes in several colors,
SSCS recommends the colorless or blue versions in 700 ml bottles,
part number: LIQ-702CL-B (clear) or LIQ-702B-B (blue), as the
dyes in the other colored versions can form small particulates when
not well mixed.
Contact Koolance for details:
Koolance USA
2840 West Valley Highway North
Auburn, WA 98001
(253) 893-7551
Water or ethylene glycol/water mixtures are also acceptable as
coolants.
Note that algae growth can occur when water is used without at
least 25% propylene or ethylene glycol.