THERMOCUBE II 200-650W THERMOELECTRIC CHILLER MANUAL 52-14790-1
SOLID STATE COOLING SYSTEMS, 167 MYERS CORNERS ROAD, WAPPINGERS FALLS, NY 12590 6
TELEPHONE: (845) 296-1300, FAX: (845) 296-1303, WEB: WWW.SSCOOLING.COM VERSION M2
SECTION 2
SPECIFICATIONS ________________________________________________
Operating Range (Set Point): 5°C to 50°C standard
(down to -5°C with low temp option - LT)
(up to 65°C with high temp option – HT, 60°C for centrifugal pumps)
Ambient Temperature Range: 10°C to 40°C non-condensing
Stability / Repeatability: ±0.05°C with constant load (even near ambient)
Cooling Capacity (typical
1
): 200-650 watts @ 20°C in 20°C ambient air (depending on model -
see cooling curves)
Heating Capacity (typical): 400-1200 watts @ 20°C in 20°C ambient air (depending on model)
Noise Level (at 1 meter): < 50 dBA (with 50% load), < 63 dBA (with full load)
Coolant / Process Fluid: Koolance (27% propylene glycol / water mix)
or 27-50% ethylene glycol / water mix
Options available for PAO, Fluorinert / Galden, HFE, or Opteon-SF10
(contact SSCS for advice on other fluids)
Process Fluid Fittings: 1/4” John Guest standard (see options section for other fitting types)
Pumps: Diaphragm, Centrifugal or Gear pumps available
(see options section for pump types and specifications)
Tank Volume: 300 ml with level sensor
Wetted Materials: Aluminum, stainless steel and polymers
(Options available for Copper "C" and Stainless Steel "S" cold plates)
Dimensions (L x W x H): 200-500w Models T22-T25: 13” x 11” x 13” (32cm x 28cm x 32cm)
650w Model T26: 14.5” x 11 x 13” (37cm x 28cm x 32cm)
Weight: 28 lbs (12.7 kg) for models T22-T25, 33lbs for model T26
Power Input: Universal Input: 100-240 VAC, 50/60 Hz,
Thermocube T22: 5 amps max @ 100VAC, 2 amps max at 240VAC
Thermocube T23: 7 amps max @ 100VAC, 2.7 amps max at 240VAC
Thermocube T24: 9 amps max @ 100 VAC, 3.5 amps max at 240VAC
Thermocube T25: 9 amps max @ 100 VAC, 3.5 amps max at 240VAC
Thermocube T26: 11 amps max @ 100VAC,4.6 amps max at 240VAC
Controls: Digital PID controller for heating and cooling
Communications: Keypad, RS232, RS485 or Ethernet
Alarms Temperature, fluid level, system or component failure
(display and RS232 option)
Standards TUV listed to UL, CAN/CSA and EN 61010-1, CE 61010-1
(RoHS compatibility is available with the "-R" option)
Other Options (see Section 7 for available options)
Warranty 2 years (diaphragm pumps are 1 year)