EasyManuals Logo

SOLIS S5-EH1P-L User Manual

SOLIS S5-EH1P-L
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
6. Operation 6. Operation
.This function should be activated only after the installation In the case of a low battery
voltage shutdown, the inverter will shut-down. This setting can be enabled, so when the
inverter detects PV or grid it wakes up the battery. This function conicts with the battery
reverse polarity protection( If the installer connects cables with wrong polarity the inverter ,
can protect itself from damage).To avoid the possible damage during installation do not ,
active battery wakeup function before finishing the first commissioning.
6.6.6.5 Battery Wakeup
6.6.7 Export power Set
Settings
Figure 6.46 Export power Set
Export power Set
2015-02-23 19 35
BackowPower
ON/OFF
FailSafe ON/OFF
This function is to set the export power control.
1.Backflow Power. 2. ON/OFF. 3.Failsafe ON/OFF
Setting 1&3 are only valid when Setting 2 is set to "ON"
"ON/OFF" is to enable/disable the export power control function
"Backflow Power" is to set the max allowed export power at the meter location
"Failsafe ON/OFF" is a protection method to prevent excess export power when meter
communication fails
Figure 6.47 Backflow Power
Settings
Backflow Power
2015-02-23 19 35
Y E S = < E N T > N O = < E S C >
Backow Power+1200W
E S C
U P
D O W N E N T
Determine the allowed backfeed power. (System export to the grid)
6.6.7.1 Backflow Power
.72..71.
Mode 4: Off-Grid Mode Logic(For Off-grid use and AC-Grid Port Disconnected)
OverDischg SOC for Off-Grid Setting Range: From Battery “Forcecharge SOC” to 100%
PV Power Using Priority: Load>Battery
Load Support Priority: PV>Battery
Battery Charging Power comes from PV.
Off Grid Mode
Path: Advanced Settings->Storage Energy Set->Storage Mode Select->Off-Grid Mode->
ON->Off Grid Mode
Settings
Off Grid Mode
2015-02-23 19 35
E S C
U P
D O W N E N T
OverDischg SOC for Off Grid: 045%
Y E S = < E N T > N O = < E S C >
Figure 6.45
E S C
U P
D O W N E N T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SOLIS S5-EH1P-L and is the answer not in the manual?

SOLIS S5-EH1P-L Specifications

General IconGeneral
BrandSOLIS
ModelS5-EH1P-L
CategoryInverter
LanguageEnglish

Related product manuals