FCAx3 USER MANUAL
A3+ CMYK
28 +44 (1753) 214 500
Cycling Off Time (mins) Minutes 1 to 255
Operation When Door is Open Normal, Off, ON
Door Open Response Time (secs) Seconds N/A, 1 to 255
Door Close Response Time (secs) Seconds N/A, 1 to 255
Operation When in Post Drip Down Recovery On or Off
Type of Load
Select the type of load connected to the relay.
Operation When Compressor is ON
Select the operation of the relay when the compressor is ON.
On = Relay will turn ON (if OFF) and remain ON when the compressor is ON.
Off = Relay will turn OFF (if ON) and remain OFF when the compressor is ON.
Cycling = Relay will cycle ON / OFF for the dened periods while the compressor is ON.
Heater = Relay will turn ON (if OFF) when the temperature is less than the heater cut-in value and turn OFF (if ON) when the
temperature is more than the heater cut-out value during compressor ON.
Light Control = Relay will turn ON (if OFF) when the compressor is ON during normal mode but will turn OFF (if ON) when the
compressor is ON during energy-saving mode.
Cycling ON Time
The duration the relay will turn ON for while the compressor is ON. After this, the relay will turn OFF.
Cycling OFF Time
The duration the relay will turn OFF for while the compressor is ON. After this, the relay will turn ON.
Operation When Compressor is OFF
Select the operation of the relay when the compressor is OFF.
On = Relay will turn ON (if OFF) and remain ON when the compressor is OFF.
Off = Relay will turn OFF (if ON) and remain OFF when the compressor is OFF
Cycling = Relay will cycle ON / OFF for the dened periods while the compressor is OFF.
Heater = Relay will turn ON (if OFF) when the temperature is less than the heater cut-in value and turn OFF (if ON) when the
temperature is more than the heater cut-out value during Compressor OFF.
Light Control = Relay will turn ON (if OFF) when the compressor is OFF during normal mode but will turn OFF (if ON) when the
compressor is OFF during energy-saving mode.
Cycling ON Time
The duration the relay will turn ON for while the compressor is OFF. After this, the relay will turn OFF.
Cycling OFF Time
The duration the relay will turn OFF for while the compressor is OFF. After this, the relay will turn ON.
Operation During Defrost
Select the operation of the relay during defrost mode.
ON = Relay will turn ON (if OFF) and remain ON during defrost mode.
OFF = Relay will turn OFF (if ON) and remain OFF during defrost mode.
Cycling = Relay will cycle ON / OFF for the dened periods during defrost mode.
Heater = Relay will turn ON (if OFF) when the temperature is less than the heater cut-in value and turn OFF (if ON) when the
temperature is more than the heater cut-out value during defrost.
Light Control = Relay will turn ON (if OFF) during defrost mode in normal mode but will turn OFF (if ON) during defrost in
energy-saving mode.
Cycling ON Time
The duration the relay will turn ON during defrost mode. After this, the relay will turn OFF.
Cycling OFF Time
The duration the relay will turn OFF during defrost mode. After this, the relay will turn ON.
Operation When Probe#1/2/3 Faulty
Select the operation of Relay #2 when a probe is faulty.