The duration of defrost during emergency defrost.
Enable Defrost During Probe#1/#2/#3 Active Faulty Mode
Select if defrost is enabled when probe #1 is faulty and Probe #1 “Type of Fault Detection” is set to Active.
No = Defrost is disabled. Defrost will not occur during probe fault regardless of if defrost parameters are satised.
Yes = Defrost is enabled. Defrost will occur when defrost parameters are satised.
10.7 VOLTAGE PROTECTION
DESCRIPTION UNIT RANGE
Enable Voltage Protection Yes or No
High Voltage Disconnect (Vac) Vac 75 to 300
High Voltage Reconnect (Vac) Vac 75 to 300
Low Voltage Disconnect (Vac) Vac 75 to 300
Low Voltage Reconnect (Vac) Vac 75 to 300
High Voltage Blind Time (secs) Seconds 0 to 25
Low Voltage Blind Time (secs) Seconds 0 to 25
Enable Voltage Protection Feature
Select whether voltage protection is active.
No = Voltage protection is disabled. All other voltage protection parameters become de-active and FCAx3 will not respond to
High or Low Voltage.
Yes = Voltage Protection is enabled. FCAx3 will act according to set parameters.
High Voltage Disconnect
The maximum allowable voltage before the FCAx3 disconnects power to all the outputs.
High Voltage Reconnect
The voltage, which the FCAx3 will reconnect power to all the outputs after a High Voltage Disconnect event.
Low Voltage Disconnect
The minimum allowable voltage before the FCAx3 disconnects power to all the outputs.
Low Voltage Reconnect
The voltage, which the FCAx3 will reconnect power to all the outputs after a Low Voltage Disconnect event.
High Voltage Blind Time
The duration that the voltage must be higher/lower than the High Voltage Disconnect/High Voltage Reconnect before
disconnecting/reconnecting power to the compressor and outputs.
Low Voltage Blind Time
The duration that the voltage must be lower/higher than the Low Voltage Disconnect/Low Voltage Reconnect before
disconnecting/reconnecting power to the compressor and outputs.
10.8 DOOR SWITCH OPERATION
DESCRIPTION UNIT RANGE
Compressor Operation When Door Switch is Open Normal or Off
Door Switch Open Persistence Duration (secs) Seconds N/A, 1 to 255
Door Switch Close Persistence Duration (secs) Seconds N/A, 1 to 255
Compressor Operation when Door Switch is Open
Select the compressor operation when a door event occurs.