14 Installation guide | Supercal 5
Error messages
The Supercal 5 indicates occurring errors by displaying on the LCD the Err-sign
together with a numbered code. If several errors occur at the same time, the
numbers of the error codes are added.
1
Temperature reference 1 A/D: A cable of
the temperature sensor is interrupted or not connected.
2
Temperature reference 2 A/D: A cable of the temperature sensor is interrupted
or not connected.
4
Temperature reference 1 A/D: A cable of the temperature sensor is conected
but its value can not be read out.
8
Temperature reference 2 A/D: A cable of the temperature sensor is connected
but its value can not be read out
16
Temperature sensor 1 < = min. Range error
32
Temperature sensor 1 > = max. Range error
64
Temperature sensor 2 < = min. Range error
128
Temperature sensor 2 > = maxß. Range error
512
The ow rate is higher than 1,5 qs
1024
The SC5 is open
2048
Power outage
4096
M1 Power Supply / M1 Unsupported / Slot left error: Error in module 1:
Details must be found into specic module error
8192
M2 Power Supply / M2 Unsupported / Slot right error : Error in module 2:
Details must be found into specic module error
Errors will be registered in the error register with its date and time (beginning) and duration
(in minutes).