Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-101-
56
Emergency stop
When this command is valid, the motor decelerate to
emergency stop as per the time set by P01.26.
57
Motor over-temperature fault
input
Motor stops at motor over-temperature fault input.
59
FVC switches to V/F control
When this terminal is valid in stop state, switch to SVPWM
control.
60
Switch to FVC control
When this terminal is valid in stop state, switch to closed-loop
vector control.
61
PID polarity switch-over
Switching the output polarity of PID, this terminal should be
used in conjunction with P09.03
66
Zero out the counter
Zero out the position counting value
67
Pulse increase
When the terminal function is valid, the pulse input is increased
according to the P21.27 pulse speed.
68
Enable pulse superimposition
When the pulse superimposition is enabled, pulse increase and
pulse decrease are effective.
69
Pulse decrease
When the terminal function is valid, the pulse input is decreased
according to the P21.27 pulse speed.
70
Electronic gear selection
When the terminal is valid, the proportional numerator is
switched to the P21.30 numerator of the 2
nd
command ratio.
71
Switch to mater
In stopped state, if the function is valid, the master is used.
72
Switch to slave
In stopped state, if the function is valid, the slave is used.
73
Reset roll diameter
Used to reset the roll diameter when the tension control function
is enabled.
74
Switch winding/unwinding
Used to switch winding/unwinding modes when the tension
control function is enabled.
75
Tension control pre-drive
If the terminal is valid when the tension control function is
enabled, tension control pre-drive is performed.
76
Disable roll diameter calculation
If the terminal is valid when the tension control function is
enabled, roll diameter calculation is disabled.
77
Clear alarm display
Used to clear the alarm display when the tension control
function is enabled.
78
Manual braking of tension
control
If the terminal is valid when the tension control function is
enabled, manual braking is activated.
79
Trigger forced feeding interrupt
If the terminal is valid when the tension control function is
enabled, a feeding interrupt signal is triggered forcibly.
80
Initial roll diameter 1
Used to select different initial roll diameters by combining with
the initial roll diameter 2 when the tension control function is
enabled.
81
Initial roll diameter 2
Used to select different initial roll diameters by combining with
the initial roll diameter 1 when the tension control function is
enabled.