Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-102-
82
Trigger fire mode control
In fire mode, if the terminal is valid, the fire mode control signal
is triggered.
83
Switch tension PID parameters
Used to switch two PID parameter groups when the tension
control function is enabled. The first group is used by default. If
the terminal is valid, the second group is used.
84–95
Reserved
/
Related parameter list:
Function
code
Name
Description
Default
value
P05.00
HDI input type
0x00–0x11
Ones: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0x00
P05.01
Function of S1 terminal
0: No function
1: Forward running
2: Reverse running
3: 3-wire control
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Running pause
9: External fault input
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switch-over between setup A and
setup B
14: Switch-over between combination
setting and A setting
15: Switch-over between combination
setting and setup B
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Multi-step speed pause
21: Acceleration/deceleration time
selection 1
22: Acceleration/deceleration time
1
P05.02
Function of S2 terminal
4
P05.03
Function of S3 terminal
7
P05.04
Function of S4 terminal
0
P05.05
Function of HDIA terminal
0
P05.06
Function of HDIB terminal
0
P05.07
Reserved
0