Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-140-
to the stop speed (P01.15), the VFD stops.
1: Coast to stop; after stop command is valid, the VFD stops
output immediately, and the load coasts to stop as per
mechanical inertia.
P01.09
Starting
frequency of DC
brake after stop
Starting frequency of DC brake after stop; during
decelerating to stop, when this frequency is reached, DC
brake will be performed after stop.
Demagnetization time (waiting time of DC brake after stop):
Before the DC brake, the VFD will block output, and after
the demagnetization time elapses, DC brake will start. This
function is used to prevent overcurrent fault caused by DC
brake during high speed.
DC brake current after stop: it means the DC brake force
applied, the larger the current, the stronger the DC brake
effect.
P01.04
Acceleration
P01.30
P01.23
Constant speed
In running
Deceleration
P01.10
P01.31
P01.12
P01.09
Time t
Setting range of P01.09: 0.00Hz–P00.03 (max. output
frequency)
Setting range of P01.10: 0.00–30.00s
Setting range of P01.11: 0.0–100.0% (of the rated VFD
output current)
Setting range of P01.12: 0.0–50.0s
0.00Hz
P01.10
Waiting time of
DC brake after
stop
0.00s
P01.11
DC brake
current of stop
0.0%
P01.12
DC brake time
of stop
0.00s
P01.13
Deadzone time
of
forward/reverse
rotation
This function code refers to the transition time of the
threshold set by P01.14 during setting forward/reverse
rotation of the VFD, as shown below.
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0–3600.0s
0.0s
P01.14
Forward/reverse
rotation switch-
over mode
0: Switch over after zero frequency
1: Switch over after starting frequency
2: Switch over after passing stop speed and delay
1
P01.15
Stop speed
0.00100.00Hz
0.50Hz
P01.16
Stop speed
0: Set value of speed (the only detection mode valid in