Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-156-
10: HDIB
11: EtherCAT/PROFITNET/Ethernet IP communication
12: PLC programmable card
13: Reserved
Set voltage value
via keypad
When the channel for voltage setup is set to "keypad",
the value of this function code is digital voltage set value.
Setting range: 0.0%–100.0%
Voltage
acceleration time
Voltage increase time means the time needed from
outputting the min. voltage to accelerating to output the
max. voltage.
Voltage decrease time means the time needed from
outputting max. voltage to outputting the min. voltage
Setting range: 0.0–3600.0s
Voltage
deceleration time
Set the upper/lower limit value of output voltage.
Vmax
Vmin
V set
Time t
t1 t2
t1=P04.29
t2=P04.30
Setting range of P04.31: P04.32–100.0% (rated motor
voltage)
Setting range of P04.32: 0.0%–P04.31
Flux-weakening
coefficient of
constant-power
zone
VF pull-in current 1
of synchronous
motor
When the synchronous motor VF control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is lower
than the frequency set in P04.36.
Setting range: -100.0%–+100.0% (of the motor rated
current)
VF pull-in current 2
of synchronous
motor
When the synchronous motor VF control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
higher than the frequency set in P04.36.
Setting range: -100.0%–+100.0% (of the motor rated
current)
VF pull-in current
frequency switch-
over threshold of
synchronous
motor
When the synchronous motor VF control mode is
enabled, this parameter is used to set the frequency
threshold for the switching between injection current 1
and injection current 2.
Setting range: 0.0%–200.0% (of the motor rated
frequency)