These function codes define the relation between analog
input voltage and corresponding set value of analog input.
When the analog input voltage exceeds the range of
max./min. input, the max. input or min. input will be adopted
during calculation.
When analog input is current input, 0–20mA current
corresponds to 0–10V voltage.
In different applications, 100% of analog setting corresponds
to different nominal values.
The figure below illustrates several settings.
Input filter time: Adjust the sensitivity of analog input,
increase this value properly can enhance the anti-
interference capacity of analog variables; however, it will
also degrade the sensitivity of analog input.
Note: AI1 can support 0–10V/0–20mA input, when AI1 selects
0–20mA input; the corresponding voltage of 20mA is 10V; AI2
supports -10V–+10V input.
Setting range of P05.24: 0.00V–P05.26
Setting range of P05.25: -300.0%–300.0%
Setting range of P05.26: P05.24–10.00V
Setting range of P05.27: -300.0%–300.0%
Setting range of P05.28: 0.000s–10.000s
Setting range of P05.29: -10.00V–P05.31
Setting range of P05.30: -300.0%–300.0%
Setting range of P05.31: P05.29–P05.33
Setting range of P05.32: -300.0%–300.0%