Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-177-
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00HzP00.03 (max. output
frequency)
Setting range of P08.33: 0.0100.0% (FDT1 level)
Setting range of P08.34: 0.00HzP00.03 (max. output
frequency)
Setting range of P08.35: 0.0–100.0% (FDT2 level)
P08.36
Detection value for
frequency arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the multi-
function digital output terminal outputs "frequency
arrival" signal as shown below.
Y1,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (max. output frequency)
0.00Hz
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
P08.38
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of energy-consumption
brake, adjust this value properly can brake the load
effectively. The default value will change with the change
of voltage class.
Setting range: 200.0–2000.0V
220V
voltage:
380.0V;
380V
voltage:
700.0V;
P08.39
Running mode of
cooling fan
0: Common running mode
1: The fan keeps running after power up
2. Running mode 2
0
P08.40
PWM selection
0x0000–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH modulation
1: PWM mode 2, 3PH modulation
Tens place: PWM low-speed carrier limit
0: Low-speed carrier limit mode 1
0x1101