Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-193-
P11.41
Fault severity
group 11
Group 8: Faults 39–42 (ENC1Z, STO, STL1, STL2)
Group 9: Faults 43–46 (STL3, CrCE, P-E1, P-E2)
Group 10: Faults 4750 (P-E3, P-E4, P-E5, P-E6)
Group 11: Faults 51–54 (P-E7, P-E8, P-E9, P-E10)
Group 12: Faults 5558 (E-Err, ENCU, E-PN, SECAN)
Group 13: Faults 59–62 (OT, F1-Er, F2-Er, F3-Er)
Group 14: Faults 63–66 (C1-Er, C2-Er, C3-Er, E-CAT)
Group 15: Faults 6770 (E-BAC, E-DEV, S-Err, OtE1)
Group 16: Faults 71–75 (OtE2, E-EIP, E-PAO, E-AI1)
Group 17: Faults 7578 (E-AI2, E-AI3, Reserved,
Reserved)
Group 18: Faults 79–82 (Reserved, Reserved,
Reserved, Reserved)
Group 19: Faults 83–86 (Reserved, Reserved,
Reserved, Reserved)
Group 20: Faults 87–90 (Reserved, Reserved,
Reserved, Reserved)
0x0000
P11.42
Fault severity
group 12
0x0000
P11.43
Fault severity
group 13
0x0000
P11.44
Fault severity
group 14
0x0000
P11.45
Fault severity
group 15
0x0000
P11.46
Fault severity
group 16
0x0000
P11.47
Fault severity
group 17
0x0000
P11.48
Fault severity
group 18
0x0000
P11.49
Fault severity
group 19
0x0000
P11.50
Fault severity
group 20
0x0000
P11.51
Action for fault pre-
alarm
0–4
0: Run at the set frequency
1: Run at the output frequency at the time of fault
2: Run at the frequency upper limit
3: Run at the frequency lower limit
4: Run at the frequency reserved for exception
0
P11.52
Frequency
reserved for
exception
0.00630.00(Hz)
0.00Hz
P11.53
Fire mode function
0–2
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P11.53=0, the fire mode is invalid, and the
normal running mode is used. In this case, the VFD
stops when encountering a fault.
When the fire mode function is valid, the VFD runs at
the speed specified by P11.54.
When fire mode 1 is selected, the VFD always runs
except when the VFD has been damaged.
When fire mode 2 is selected, the VFD always runs, but
the VFD stops when encountering OUT1, OUT2,
OUT3, OC1, OC2, OC3, OV1, OV2, OV3, or SPO.
Note: Terminal control must be used for a fire mode.
0