Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-211-
P17.32
Motor flux linkage
0.0%200.0%
0.0%
P17.33
Exciting current
reference
Display the exciting current reference value under
vector control mode
Range: -3000.03000.0A
0.0A
P17.34
Torque current
reference
Display torque current reference value under vector
control mode
Range: -3000.03000.0A
0.0A
P17.35
AC incoming current
Display the valid value of incoming current on AC side
Range: 0.0–5000.0A
0.0A
P17.36
Output torque
Display output torque value, during forward running,
positive value is motoring state, negative value is
generating state; during reverse running, positive
value is generating state, negative value is motoring
state.
Range: -3000.0Nm–3000.0Nm
0.0Nm
P17.37
Motor overload count
value
0–65535
0
P17.38
Process PID output
-100.0%–100.0%
0.0%
P17.39
Parameter download
wrong function code
0.0099.00
0.00
P17.40
Motor control mode
0x0000x123
Ones: Control mode
0: Vector 0
1: Vector 1
2: VF control
3: Closed-loop vector control
Tens: Control state
0: Speed control
1: Torque control
2: Position control
Hundreds: Motor number
0: Motor 1
1: Motor 2
0x000
P17.41
Upper limit of the
torque when
motoring
0.0%300.0% (rated motor current)
0.0%
P17.42
Upper limit of brake
torque
0.0%300.0% (rated motor current)
0.0%
P17.43
Upper limit frequency
of forward running of
torque control
0.00P00.03
0.00Hz
P17.44
Upper limit frequency
of reverse running of
0.00P00.03
0.00Hz