Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-219-
Tens: Sin/Cos encoder
0: without CD signal
1: with CD signal
P20.15
Speed
measurement
mode
0: PG card
1: local; realized by HDIA and HDIB; supports
incremental 24V encoder only
0
P20.16
Frequency-division
coefficient
0–255
0
P20.17
Pulse filer
processing
0x00000xFFFF
Bit0: Enable/disable encoder input filter
0: No filter
1: Filter
Bit1: Encoder signal filter mode (set Bit0 or Bit2 to 1)
0: Self-adaptive filter
1: Use P20.18 filter parameters
Bit2: Enable/disable encoder frequency-division output
filter
0: No filter
1: Filter
Bit3: Reserved
Bit4: Enable/disable pulse reference filter
0: No filter
1: Filter
Bit5: Pulse reference filter mode (valid when Bit4 is set
to 1)
0: Self-adaptive filter
1: Use P20.19 filter parameters
Bit615: Reserved
0x0033
P20.18
Encoder pulse
filter width
0–63
0 means 0.25μs
2
P20.19
Pulse reference
filter width
0–63
0 means 0.25μs
2
P20.20
Pulse number of
pulse reference
0–65535
1024
P20.21
Enable angle
compensation of
synchronous
motor
0–1
1
P20.22
Switch-over
frequency
threshold of speed
measurement
mode
0–630.00Hz
1.00Hz
P20.23
Synchronous
motor angle
compensation
-200.0200.0%
100.0%