Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-223-
1: Valid
Bit8: Positioning enable signal selection (for cyclic
positioning by terminals only; positioning function is
always enabled for automatic cyclic positioning)
0: Pulse signal
1: Level signal
Bit9: Position source
0: P21.17 setting
1: PROFIBUS/CANopen setting
Bit10: Whether to save the encoder pulse counting
value at power failure
0: Do not save
1: Save
Bit 11: Reserved
Bit12: Positioning curve selection (reserved)
0: Straight line
1: S curve
Position digital
reference
Set digital positioning position;
Actual position=P21.17×P21.11/P21.12
0–65535
Positioning speed
setup selection
0: Set by P21.19
1: Set by AI1
2: Set by AI2
3: Set by AI3
4: Set by high speed pulse HDIA
5: Set by high speed pulse HDIB
Acceleration time
of positioning
Set the acceleration/deceleration time of positioning
process.
Acceleration time of positioning means the time needed
for the VFD to accelerate from 0Hz to the max. output
frequency (P00.03).
Deceleration time of positioning means the time needed
for the VFD to decelerate from the max. output frequency
(P00.03) to 0hz.
Setting range of P21.20: 0.01–300.00s
Setting range of P21.21: 0.01–300.00s
Deceleration time
of positioning
Hold time of
positioning arrival
Set the hold time of waiting when target positioning
position is reached.
Setting range: 0.000–60.000s