Frequency Inverter ST600 Series High-Performance Multifunction VFD Communication protocol
-280-
9.3.1.2 Application to multiple VFDs
In practical application to multiple VFDs, chrysanthemum connection and star connection are
commonly used.
According to the requirements of the RS485 industrial bus standards, all the devices need to be
connected in chrysanthemum mode with one 120 Ω terminal resistor on each end, as shown in Figure
9-3. Figure 9-4 is the simplified wiring diagram, and Figure 9-5 is the practical application diagram.
Figure 9-3 On-site chrysanthemum connection diagram
1# 2
#
3 # 4 # 32 #
120Ω
120Ω
Figure 9-4 Simplified chrysanthemum connection diagram
1# 2# 3# 31#Master
A+
B-
A+ B-
Figure 9-5 Practical application diagram of chrysanthemum connection
Figure 9-6 shows the start connection diagram. When this connection mode is adopted, the two
devices that are farthest away from each other on the line must be connected with a terminal resistor
(in Figure 9-6, the two devices are devices 1# and 15#).
ST
VFD
Address 1
Earth
485+
485-
485+
485-
485+
485-
120Ω
Terminal
resistor
PC
Converter
GND
RS232-RS485
Max. length of the
cable: 15 m
Shielded twisted pair
Address 2 Address N
ST
VFD
ST
VFD
Earth Earth